Tuesday, 8 July 2014

Fire Fighting System India


A fire fighting system is probably the most important of the building services, as its aim is to protect human life and property, strictly in that order.  

It consists of three basic parts:
  •  fire storage tanks
  • a specialised pumping system,  
  • a large network of pipes ending in either hydrants or sprinklers 
fire hydrant is a vertical steel pipe with an outlet, close to which two fire hoses are stored . During a fire, firefighters will go to the outlet, break open the hoses, attach one to the outlet, and manually open it so that water rushes out of the nozzle of the hose. The quantity and speed of the water is so great that it can knock over the firefighter holding the hose if he is not standing in the correct way.  As soon as the fire fighter opens the hydrant, water will gush out, and sensors will detect a drop in pressure in the system. This drop in pressure will trigger the fire pumps to turn on and start pumping water at a tremendous flowrate.




sprinkler is a nozzle attached to a network of pipes, and installed just below the ceiling of a room. Every sprinkler has a small glass bulb with a liquid in it. This bulb normally blocks the flow of water. In a fire, the liquid in the bulb will become hot. It will then expand, and shatter the glass bulb, removing the obstacle and causing water to spray from the sprinkler. The main difference between a hydrant and a sprinkler is that a sprinkler will come on automatically in a fire. A fire hydrant has to be operated manually by trained firefighters - it cannot be operated by laymen. A sprinkler will usually be activated very quickly in a fire - possibly before the fire station has been informed of the fire - and therefore is very effective at putting out a fire in the early stages, before it grows into a large fire.  For this reason, a sprinkler system is considered very good at putting out fires before they spread and become unmanageable.  

Wednesday, 4 June 2014

Fire Alarm Systems Kerala


All Fire Alarm Systems essentially operate on the same principle. If a detector detects smoke or heat or someone operates a break glass unit (manual break point), then alarm sounders operate to warn others in the building that there may be a fire and to evacuate. It may also incorporate remote signaling equipment which would alert the fire brigade via a central station.
Fire Alarm Systems can be broken down into four categories:
  • Conventional
  • Analogue Addressable
  • Addressable
  • Wireless systems

Conventional Fire Alarm System

In a Conventional Fire Alarm System, a number of call points and detectors are wired to the Fire Alarm Control Panel in Zones. A Zone is a circuit and typically one would wire a circuit per floor or fire compartment. The Fire Alarm Control Panel has a number of Zone Lamps. The reason for having Zones is to give a rough idea as to where a fire has occurred. This is important for the fire brigade and of course for the building management. The accuracy of knowing where a fire has started is controlled by the number of Zones a Control Panel has and the number of circuits that have been wired within the building. The Control Panel is wired to a minimum of two sounder circuits which could contain bells, electronic sounders or other audible devices. Each circuit has an end of line device which is used for monitoring purposes.

Addressable Systems

The detection principle of an Addressable System is similar to a Conventional System except that the Control Panel can determine exactly which detector or call point has initiated the alarm. The detection circuit is wired as a loop and up to 99 devices may be connected to each loop. The detectors are essentially Conventional Detectors, with an address built in. The address in each detector is set by dil switches and the Control Panel is programmed to display the information required when that particular detector is operated. Additional Field Devices are available which may be wired to the loop for detection only i.e. it is possible to detect a normally open contact closing such as sprinkler flow switch, or a normally closed contact opening. Sounders are wired in a minimum of two sounder circuits exactly as a Conventional System. Loop Isolation Modules are available for fitting on to the detection loop/loops such that the loop is sectioned in order to ensure that a short circuit, or one fault will only cause the loss of a minimal part of the system.




Analogue Addressable Fire Alarm Systems

Analogue Addressable Fire Alarm Systems are often known as Intelligent Fire Alarm Systems. There are several different types of Analogue Systems available which are determined by the type of protocol which they use. The bulk of standard Analogue Detectors available are fairly stupid as the Detectors can only give output signals representing the value of detected phenomena. It is left up to the Control Unit to decide whether there is a fire, fault, pre-alarm or other. With a true Intelligent Analogue System each detector effectively incorporates its own computer which evaluates the environment around it, and communicates to the Control Panel whether there is a fire, fault or the detector head needs cleaning. Essentially Analogue Systems are far more complex and incorporate far more facilities than Conventional or Addressable Systems. Their primary purpose is to help prevent the occurrence of false alarms. With the Analogue Addressable System, up to 127 input devices i.e.: Smoke Detectors, Call Points, Heat Detectors, Contact Monitors and other interface devices may be wired to each detection loop. In addition to the 127 Input Devices, up to 32 Output Devices such as Loop Sounders, Relay Modules and Sounder Modules may be connected. Analogue Systems are available in 2, 4 and 8 loop versions which means large premises can be monitored from one single panel. Isolator units should be connected between sections of detectors as described for Addressable Systems.



Wireless Fire Alarm System

Wireless fire alarm systems are an effective alternative to traditional wired fire alarm systems for all applications. They utilise secure, licence-free radio communications to interconnect the sensors and devices (smoke detectors, call-points, etc.) with the controllers. It is a simple concept, which provides many unique benefits and is a full analogue addressable fire detection system without the need for cable.






Friday, 2 May 2014

Fire sprinklers and fire pumps

End Suction Fire Pumps :

Dutch Tech’s new range of UL listed and FM approved fire pumps provides you a reliable solution for your fire fighting pump needs by combining the stringent quality measures of UL and NFPA standards with our proven experience in the fire protection field.We can offer you a complete package of service starting from engineering assistance to field start-up and periodic maintenance. Each pump set is tested in our factory, prior to dispatch, as per UL and NFPA standards. These pumps are covered by a warranty of one year subject to standard terms and conditions.
Accessories:
A complete and reliable fire protection system requires various mechanical and hydraulic accessories. However, the requirements will vary to fit the specific needs of each individual installation and the standards of the Authorities having Jurisdiction. The accessories recommended by the current edition of National Fire Protection Association pamphlet No. 20 include: casing relief valve, suction and discharge gauges, main relief valve, flow meter, concentric discharge increaser, eccentric suction reducer, increasing discharge tee,over flow cone, hose valve head, hose valve caps and chains, ball drip valve and automatic air release valve (not required for end suction pumps).





Friday, 11 April 2014

Fire Alarm System India

Instead of reporting alarms by general location or zones,  Intelligent Fire Alarm Controllers (IFC) can zero in on each device and identify its specific location and status, saving time and confusion in an emergency. As your business needs change, the modular design of controllers lets you network additional Fire Alarm Control panels or add new devices as your facility grows. This flexibility means substantial cost savings in your investment. It offers intelligent addressable systems ranging from small single alarm panel systems to complete, networkable solutions for large-scale applications.